home *** CD-ROM | disk | FTP | other *** search
Text File | 1993-08-26 | 50.5 KB | 1,205 lines |
- /* Part 4 of 4 of accesibility requirements follow. */
-
- A4.1.3 Accessible Buildings: New Construction.
-
- A4.1.3(5) Only full passenger elevators are covered by the
- accessibility provisions of 4.10. Materials and equipment
- hoists, freight elevators not intended for passenger use,
- dumbwaiters, and construction elevators are not covered by these
- guidelines. If a building is exempt from the elevator
- requirement, it is not necessary to provide a platform lift or
- other means of vertical access in lieu of an elevator.
-
- Under Exception 4, platform lifts are allowed where existing
- conditions make it impractical to install a ramp or elevator.
- Such conditions generally occur where it is essential to provide
- access to small raised or lowered areas where space may not be
- available for a ramp. Examples include, but are not limited to,
- raised pharmacy platforms, commercial offices raised above a
- sales floor, or radio and news booths.
-
- A4.1.3(9) Supervised automatic sprinkler systems have built in
- signals for monitoring features of the system such as the opening
- and closing of water control valves, the power supplies for
- needed pumps, water tank levels, and for indicating conditions
- that will impair the satisfactory operation of the sprinkler
- system. Because of these monitoring features, supervised
- automatic sprinkler systems have a high level of satisfactory
- performance and response to fire conditions.
-
- A4.1.3(10) If an odd number of drinking fountains is provided on
- a floor, the requirement in 4.1.3(10)(b) may be met by rounding
- down the odd number to an even number and calculating 50% of the
- even number. When more than one drinking fountain on a floor is
- required to comply with 4.15, those fountains should be dispersed
- to allow wheelchair users convenient access. For example, in a
- large facility such as a convention center that has water
- fountains at several locations on a floor, the accessible water
- fountains should be located so that wheelchair users do not have
- to travel a greater distance than other people to use a drinking
- fountain.
-
- A4.1.3(17)(b) In addition to the requirements of section
- 4.1.3(17)(b), the installation of additional volume controls is
- encouraged. Volume controls may be installed on any telephone.
-
- A4.1.3(19)(a) Readily removable or folding seating units may be
- installed in lieu of providing an open space for wheelchair
- users. Folding seating units are usually two fixed seats that
- can be easily folded into a fixed center bar to allow for one or
- two open spaces for wheelchair users when necessary. These units
- are more easily adapted than removable seats which generally
- require the seat to be removed in advance by the facility
- management.
-
- Either a sign or a marker placed on seating with removable or
-
- folding arm rests is required by this section. Consideration
- should be given for ensuring identification of such seats in a
- darkened theater. For example, a marker which contrasts (light
- on dark or dark on light) and which also reflects light could be
- placed on the side of such seating so as to be visible in a
- lighted auditorium and also to reflect light from a flashlight.
-
- A4.1.6 Accessible Buildings: Alterations.
-
- A4.1.6(1)(h) When an entrance is being altered, it is preferable
- that those entrances being altered be made accessible to the
- extent feasible.
-
- A4.2 Space Allowances and Reach Ranges.
-
- A4.2.1 Wheelchair Passage Width.
-
- (1) Space Requirements for Wheelchairs. Many persons who
- use wheelchairs need a 30 in (760 mm) clear opening width for
- doorways, gates, and the like, when the latter are entered
- head-on. If the person is unfamiliar with a building, if
- competing traffic is heavy, if sudden or frequent movements are
- needed, or if the wheelchair must be turned at an opening, then
- greater clear widths are needed. For most situations, the
- addition of an inch of leeway on either side is sufficient.
- Thus, a minimum clear width of 32 in (815 mm) will provide
- adequate clearance. However, when an opening or a restriction in
- a passageway is more than 24 in (610 mm) long, it is essentially
- a passageway and must be at least 36 in (915 mm) wide.
-
- (2) Space Requirements for Use of Walking Aids. Although
- people who use walking aids can maneuver through clear width
- openings of 32 in (815 mm), they need 36 in (915 mm) wide
- passageways and walks for comfortable gaits. Crutch tips, often
- extending down at a wide angle, are a hazard in narrow
- passageways where they might not be seen by other pedestrians.
- Thus, the 36 in (915 mm) width provides a safety allowance both
- for the person with a disability and for others.
-
- (3) Space Requirements for Passing. Able-bodied persons
- in winter clothing, walking straight ahead with arms swinging,
- need 32 in (815 mm) of width, which includes 2 in (50 mm) on
- either side for sway, and another 1 in (25 mm) tolerance on
- either side for clearing nearby objects or other pedestrians.
- Almost all wheelchair users and those who use walking aids can
- also manage within this 32 in (815 mm) width for short distances.
- Thus, two streams of traffic can pass in 64 in (1625 mm) in a
- comfortable flow. Sixty inches (1525 mm) provides a minimum
- width for a somewhat more restricted flow. If the clear width is
- less than 60 in (1525 mm), two wheelchair users will not be able
- to pass but will have to seek a wider place for passing.
- Forty-eight inches (1220 mm) is the minimum width needed for an
- ambulatory person to pass a nonambulatory or semi-ambulatory
- person. Within this 48 in (1220 mm) width, the ambulatory person
- will have to twist to pass a wheelchair user, a person with a
- service animal, or a semi-ambulatory person. There will be
- little leeway for swaying or missteps (see Fig. A1).
-
- A4.2.3 Wheelchair Turning Space. These guidelines specify a
- minimum space of 60 in (1525 mm) diameter or a 60 in by 60 in
- (1525 mm by 1525 mm) T-shaped space for a pivoting 180-degree
- turn of a wheelchair. This space is usually satisfactory for
- turning around, but many people will not be able to turn without
- repeated tries and bumping into surrounding objects. The space
- shown in Fig. A2 will allow most wheelchair users to complete
- U-turns without difficulty.
-
- A4.2.4 Clear Floor or Ground Space for Wheelchairs. The
- wheelchair and user shown in Fig. A3 represent typical dimensions
- for a large adult male. The space requirements in this guideline
- are based upon maneuvering clearances that will accommodate most
- wheelchairs. Fig. A3 provides a uniform reference for design not
- covered by this guideline.
-
- A4.2.5 & A4.2.6 Reach. Reach ranges for persons seated in
- wheelchairs may be further clarified by Fig. A3(a). These
- drawings approximate in the plan view the information shown in
- Fig. 4, 5, and 6.
-
- A4.3 Accessible Route.
-
- A4.3.1 General.
-
- (1) Travel Distances. Many people with mobility
- impairments can move at only very slow speeds; for many,
- traveling 200 ft (61
- m) could take about 2 minutes. This assumes a rate of about 1.5
- ft/s (455 mm/s) on level ground. It also assumes that the
- traveler would move continuously. However, on trips over 100 ft
- (30 m), disabled people are apt to rest frequently, which
- substantially increases their trip times. Resting periods of 2
- minutes for every 100 ft (30 m) can be used to estimate travel
- times for people with severely limited stamina. In inclement
- weather, slow progress and resting can greatly increase a
- disabled person's exposure to the elements.
-
- (2) Sites. Level, indirect routes or those with running
- slopes lower than 1:20 can sometimes provide more convenience
- than direct routes with maximum allowable slopes or with ramps.
-
- A4.3.10 Egress. Because people with disabilities may visit, be
- employed or be a resident in any building, emergency management
- plans with specific provisions to ensure their safe evacuation
- also play an essential role in fire safety and life safety.
-
- A4.3.11.3 Stairway Width. A 48 in (1220 mm) wide exit stairway
- is needed to allow assisted evacuation (e.g., carrying a person
- in a wheelchair) without encroaching on the exit path for
- ambulatory persons.
-
- A4.3.11.4 Two-way Communication. It is essential that emergency
- communication not be dependent on voice communications alone
- because the safety of people with hearing or speech impairments
- could be jeopardized. The visible signal requirement could be
- satisfied with something as simple as a button in the area of
- rescue assistance that lights, indicating that help is on the
- way, when the message is answered at the point of entry.
-
- A4.4 Protruding Objects.
-
- A4.4.1 General. Service animals are trained to recognize and
- avoid hazards. However, most people with severe impairments of
- vision use the long cane as an aid to mobility. The two
- principal cane techniques are the touch technique, where the cane
- arcs from side to side and touches points outside both shoulders;
- and the diagonal technique, where the cane is held in a
- stationary position diagonally across the body with the cane tip
- touching or just above the ground at a point outside one shoulder
- and the handle or grip extending to a point outside the other
- shoulder. The touch technique is used primarily in uncontrolled
- areas, while the diagonal technique is used primarily in certain
- limited, controlled, and familiar environments. Cane users are
- often trained to use both techniques.
-
- Potential hazardous objects are noticed only if they fall within
- the detection range of canes (see Fig. A4). Visually impaired
- people walking toward an object can detect an overhang if its
- lowest surface is not higher than 27 in (685 mm). When walking
- alongside protruding objects, they cannot detect overhangs.
- Since proper cane and service animal techniques keep people away
- from the edge of a path or from walls, a slight overhang of no
- more than 4 in (100 mm) is not hazardous.
-
- A4.5 Ground and Floor Surfaces.
-
- A4.5.1 General. People who have difficulty walking or
- maintaining balance or who use crutches, canes, or walkers, and
- those with restricted gaits are particularly sensitive to
- slipping and tripping hazards. For such people, a stable and
- regular surface is necessary for safe walking, particularly on
- stairs. Wheelchairs can be propelled most easily on surfaces
- that are hard, stable, and regular. Soft loose surfaces such as
- shag carpet, loose sand or gravel, wet clay, and irregular
- surfaces such as cobblestones can significantly impede wheelchair
- movement.
-
- Slip resistance is based on the frictional force necessary to
- keep a shoe heel or crutch tip from slipping on a walking surface
- under conditions likely to be found on the surface. While the
- dynamic coefficient of friction during walking varies in a
- complex and non-uniform way, the static coefficient of friction,
- which can be measured in several ways, provides a close
- approximation of the slip resistance of a surface. Contrary to
- popular belief, some slippage is necessary to walking, especially
- for persons with restricted gaits; a truly "non-slip" surface
- could not be negotiated.
-
- The Occupational Safety and Health Administration recommends that
- walking surfaces have a static coefficient of friction of 0.5. A
- research project sponsored by the Architectural and
- Transportation Barriers Compliance Board (Access Board) conducted
- tests with persons with disabilities and concluded that a higher
- coefficient of friction was needed by such persons. A static
- coefficient of friction of 0.6 is recommended for accessible
- routes and 0.8 for ramps.
-
- It is recognized that the coefficient of friction varies
- considerably due to the presence of contaminants, water, floor
- finishes, and other factors not under the control of the designer
- or builder and not subject to design and construction guidelines
- and that compliance would be difficult to measure on the building
- site. Nevertheless, many common building materials suitable for
- flooring are now labeled with information on the static
- coefficient of friction. While it may not be possible to compare
- one product directly with another, or to guarantee a constant
- measure, builders and designers are encouraged to specify
- materials with appropriate values. As more products include
- information on slip resistance, improved uniformity in
- measurement and specification is likely. The Access Board's
- advisory guidelines on Slip Resistant Surfaces provides
- additional information on this subject.
-
- Cross slopes on walks and ground or floor surfaces can cause
- considerable difficulty in propelling a wheelchair in a straight
- line.
-
- A4.5.3 Carpet. Much more needs to be done in developing both
- quantitative and qualitative criteria for carpeting (i.e.,
- problems associated with texture and weave need to be studied).
- However, certain functional characteristics are well established.
- When both carpet and padding are used, it is desirable to have
- minimum movement (preferably none) between the floor and the pad
- and the pad and the carpet which would allow the carpet to hump
- or warp. In heavily trafficked areas, a thick, soft (plush) pad
- or cushion, particularly in combination with long carpet pile,
- makes it difficult for individuals in wheelchairs and those with
- other ambulatory disabilities to get about. Firm carpeting can
- be achieved through proper selection and combination of pad and
- carpet, sometimes with the elimination of the pad or cushion, and
- with proper installation. Carpeting designed with a weave that
- causes a zig-zag effect when wheeled across is strongly
- discouraged.
-
- A4.6 Parking and Passenger Loading Zones.
-
- A4.6.3 Parking Spaces. The increasing use of vans with side-
- mounted lifts or ramps by persons with disabilities has
- necessitated some revisions in specifications for parking spaces
- and adjacent access aisles. The typical accessible parking space
- is 96 in (2440 mm) wide with an adjacent 60 in (1525 mm) access
- aisle. However, this aisle does not permit lifts or ramps to be
- deployed and still leave room for a person using a wheelchair or
- other mobility aid to exit the lift platform or ramp. In tests
- conducted with actual lift/van/wheelchair combinations, (under a
- Board-sponsored Accessible Parking and Loading Zones Project)
- researchers found that a space and aisle totaling almost 204 in
- (5180 mm) wide was needed to deploy a lift and exit conveniently.
- The "van accessible" parking space required by these guidelines
- provides a 96 in (2440 mm) wide space with a 96 in (2440 mm)
- adjacent access aisle which is just wide enough to maneuver and
- exit from a side mounted lift. If a 96 in (2440 mm) access aisle
- is placed between two spaces, two "van accessible" spaces are
- created. Alternatively, if the wide access aisle is provided at
- the end of a row (an area often unused), it may be possible to
- provide the wide access aisle without additional space (see Fig.
- A5(a)).
-
- A sign is needed to alert van users to the presence of the wider
- aisle, but the space is not intended to be restricted only to
- vans.
-
- "Universal" Parking Space Design. An alternative to the
- provision of a percentage of spaces with a wide aisle, and the
- associated need to include additional signage, is the use of what
- has been called the "universal" parking space design. Under this
- design, all accessible spaces are 132 in (3350 mm) wide with a 60
- in (1525 mm) access aisle (see Fig. A5(b)). One advantage to
- this design is that no additional signage is needed because all
- spaces can accommodate a van with a side-mounted lift or ramp.
- Also, there is no competition between cars and vans for spaces
- since all spaces can accommodate either. Furthermore, the wider
- space permits vehicles to park to one side or the other within
- the 132 in (3350 mm) space to allow persons to exit and enter the
- vehicle on either the driver or passenger side, although, in some
- cases, this would require exiting or entering without a marked
- access aisle.
-
- An essential consideration for any design is having the access
- aisle level with the parking space. Since a person with a
- disability, using a lift or ramp, must maneuver within the access
- aisle, the aisle cannot include a ramp or sloped area. The access
- aisle must be connected to an accessible route to the appropriate
- accessible entrance of a building or facility. The parking access
- aisle must either blend with the accessible route or have a curb
- ramp complying with 4.7. Such a curb ramp opening must be located
- within the access aisle boundaries, not within the parking space
- boundaries. Unfortunately, many facilities are designed with a
- ramp that is blocked when any vehicle parks in the accessible
- space. Also, the required dimensions of the access aisle cannot
- be restricted by planters, curbs or wheel stops.
-
- A4.6.4 Signage. Signs designating parking places for disabled
- people can be seen from a driver's seat if the signs are mounted
- high enough above the ground and located at the front of a
- parking space.
-
- A4.6.5 Vertical Clearance. High-top vans, which disabled people
- or transportation services often use, require higher clearances
- in parking garages than automobiles.
-
- A4.8 Ramps.
-
- A4.8.1 General. Ramps are essential for wheelchair users if
- elevators or lifts are not available to connect different levels.
- However, some people who use walking aids have difficulty with
- ramps and prefer stairs.
-
- A4.8.2 Slope and Rise. Ramp slopes between 1:16 and 1:20 are
- preferred. The ability to manage an incline is related to both
- its slope and its length. Wheelchair users with disabilities
- affecting their arms or with low stamina have serious difficulty
- using inclines. Most ambulatory people and most people who use
- wheelchairs can manage a slope of 1:16. Many people cannot
- manage a slope of 1:12 for 30 ft (9 m).
-
- A4.8.4 Landings. Level landings are essential toward maintaining
- an aggregate slope that complies with these guidelines. A ramp
- landing that is not level causes individuals using wheelchairs to
- tip backward or bottom out when the ramp is approached.
-
- A4.8.5 Handrails. The requirements for stair and ramp handrails
- in this guideline are for adults. When children are principal
- users in a building or facility, a second set of handrails at an
- appropriate height can assist them and aid in preventing
- accidents.
-
- A4.9 Stairs.
-
- A4.9.1 Minimum Number. Only interior and exterior stairs
- connecting levels that are not connected by an elevator, ramp, or
- other accessible means of vertical access have to comply with
- 4.9.
-
- A4.10 Elevators.
-
- A4.10.6 Door Protective and Reopening Device. The required door
- reopening device would hold the door open for 20 seconds if the
- doorway remains obstructed. After 20 seconds, the door may begin
- to close. However, if designed in accordance with ASME
- A17.1-1990, the door closing movement could still be stopped if a
- person or object exerts sufficient force at any point on the door
- edge.
-
- A4.10.7 Door and Signal Timing for Hall Calls. This paragraph
- allows variation in the location of call buttons, advance time
- for warning signals, and the door-holding period used to meet the
- time requirement.
-
- A4.10.12 Car Controls. Industry-wide standardization of elevator
- control panel design would make all elevators significantly more
- convenient for use by people with severe visual impairments. In
- many cases, it will be possible to locate the highest control on
- elevator panels within 48 in (1220 mm) from the floor.
-
- A4.10.13 Car Position Indicators. A special button may be
- provided that would activate the audible signal within the given
- elevator only for the desired trip, rather than maintaining the
- audible signal in constant operation.
-
- A4.10.14 Emergency Communications. A device that requires no
- handset is easier to use by people who have difficulty reaching.
- Also, small handles on handset compartment doors are not usable
- by people who have difficulty grasping.
-
- Ideally, emergency two-way communication systems should provide
- both voice and visual display intercommunication so that persons
- with hearing impairments and persons with vision impairments can
- receive information regarding the status of a rescue. A voice
- intercommunication system cannot be the only means of
- communication because it is not accessible to people with speech
- and hearing impairments. While a voice intercommunication system
- is not required, at a minimum, the system should provide both an
- audio and visual indication that a rescue is on the way.
-
- A4.11 Platform Lifts (Wheelchair Lifts).
-
- A4.11.2 Other Requirements. Inclined stairway chairlifts, and
- inclined and vertical platform lifts (wheelchair lifts) are
- available for short-distance, vertical transportation of people
- with disabilities. Care should be taken in selecting lifts as
- some lifts are not equally suitable for use by both wheelchair
- users and semi-ambulatory individuals.
-
- A4.12 Windows.
-
- A4.12.1 General. Windows intended to be operated by occupants in
- accessible spaces should comply with 4.12.
-
- A4.12.2 Window Hardware. Windows requiring pushing, pulling, or
- lifting to open (for example, double-hung, sliding, or casement
- and awning units without cranks) should require no more than 5
- lbf (22.2 N) to open or close. Locks, cranks, and other window
- hardware should comply with 4.27.
-
- A4.13 Doors.
-
- A4.13.8 Thresholds at Doorways. Thresholds and surface height
- changes in doorways are particularly inconvenient for wheelchair
- users who also have low stamina or restrictions in arm movement
- because complex maneuvering is required to get over the level
- change while operating the door.
-
- A4.13.9 Door Hardware. Some disabled persons must push against a
- door with their chair or walker to open it. Applied kickplates
- on doors with closers can reduce required maintenance by
- withstanding abuse from wheelchairs and canes. To be effective,
- they should cover the door width, less approximately 2 in (51
- mm), up to a height of 16 in (405 mm) from its bottom edge and be
- centered across the width of the door.
-
- A4.13.10 Door Closers. Closers with delayed action features give
- a person more time to maneuver through doorways. They are
- particularly useful on frequently used interior doors such as
- entrances to toilet rooms.
-
- A4.13.11 Door Opening Force. Although most people with
- disabilities can exert at least 5 lbf (22.2N), both pushing and
- pulling from a stationary position, a few people with severe
- disabilities cannot exert 3 lbf (13.13N). Although some people
- cannot manage the allowable forces in this guideline and many
- others have difficulty, door closers must have certain minimum
- closing forces to close doors satisfactorily. Forces for pushing
- or pulling doors open are measured with a push-pull scale under
- the following conditions:
-
- (1) Hinged doors: Force applied perpendicular to the door
- at the door opener or 30 in (760 mm) from the hinged side,
- whichever is farther from the hinge.
-
- (2) Sliding or folding doors: Force applied parallel to
- the door at the door pull or latch.
-
- (3) Application of force: Apply force gradually so that
- the applied force does not exceed the resistance of the door. In
- high-rise buildings, air-pressure differentials may require a
- modification of this specification in order to meet the
- functional intent.
-
- A4.13.12 Automatic Doors and Power-Assisted Doors. Sliding
- automatic doors do not need guard rails and are more convenient
- for wheelchair users and visually impaired people to use. If
- slowly opening automatic doors can be reactivated before their
- closing cycle is completed, they will be more convenient in busy
- doorways.
-
- A4.15 Drinking Fountains and Water Coolers.
-
- A4.15.2 Spout Height. Two drinking fountains, mounted side by
- side or on a single post, are usable by people with disabilities
- and people who find it difficult to bend over.
-
- A4.16 Water Closets.
-
- A4.16.3 Height. Height preferences for toilet seats vary
- considerably among disabled people. Higher seat heights may be
- an advantage to some ambulatory disabled people, but are often a
- disadvantage for wheelchair users and others. Toilet seats 18 in
- (455 mm) high seem to be a reasonable compromise. Thick seats
- and filler rings are available to adapt standard fixtures to
- these requirements.
-
- A4.16.4 Grab Bars. Fig. A6(a) and (b) show the diagonal and side
- approaches most commonly used to transfer from a wheelchair to a
- water closet. Some wheelchair users can transfer from the front
- of the toilet while others use a 90-degree approach. Most people
- who use the two additional approaches can also use either the
- diagonal approach or the side approach.
-
- A4.16.5 Flush Controls. Flush valves and related plumbing can be
- located behind walls or to the side of the toilet, or a toilet
- seat lid can be provided if plumbing fittings are directly behind
- the toilet seat. Such designs reduce the chance of injury and
- imbalance caused by leaning back against the fittings. Flush
- controls for tank-type toilets have a standardized mounting
- location on the left side of the tank (facing the tank). Tanks
- can be obtained by special order with controls mounted on the
- right side. If administrative authorities require flush controls
- for flush valves to be located in a position that conflicts with
- the location of the rear grab bar, then that bar may be split or
- shifted toward the wide side of the toilet area.
-
- A4.17 Toilet Stalls.
-
- A4.17.3 Size and Arrangement. This section requires use of the
- 60 in (1525 mm) standard stall (Figure 30(a)) and permits the 36
- in (915 mm) or 48 in (1220 mm) wide alternate stall (Figure
- 30(b)) only in alterations where provision of the standard stall
- is technically infeasible or where local plumbing codes prohibit
- reduction in the number of fixtures. A standard stall provides a
- clear space on one side of the water closet to enable persons who
- use wheelchairs to perform a side or diagonal transfer from the
- wheelchair to the water closet. However, some persons with
- disabilities who use mobility aids such as walkers, canes or
- crutches are better able to use the two parallel grab bars in the
- 36 in (915 mm) wide alternate stall to achieve a standing
- position.
-
- In large toilet rooms, where six or more toilet stalls are
- provided, it is therefore required that a 36 in (915 mm) wide
- stall with parallel grab bars be provided in addition to the
- standard stall required in new construction. The 36 in (915 mm)
- width is necessary to achieve proper use of the grab bars; wider
- stalls would position the grab bars too far apart to be easily
- used and narrower stalls would position the grab bars too close
- to the water closet. Since the stall is primarily intended for
- use by persons using canes, crutches and walkers, rather than
- wheelchairs, the length of the stall could be conventional. The
- door, however, must swing outward to ensure a usable space for
- people who use crutches or walkers.
-
- A4.17.5 Doors. To make it easier for wheelchair users to close
- toilet stall doors, doors can be provided with closers, spring
- hinges, or a pull bar mounted on the inside surface of the door
- near the hinge side.
-
- A4.19 Lavatories and Mirrors.
-
- A4.19.6 Mirrors. If mirrors are to be used by both ambulatory
- people and wheelchair users, then they must be at least 74 in
- (1880 mm) high at their topmost edge. A single full length
- mirror can accommodate all people, including children.
-
- A4.21 Shower Stalls.
-
- A4.21.1 General. Shower stalls that are 36 in by 36 in (915 mm
- by 915 mm) wide provide additional safety to people who have
- difficulty maintaining balance because all grab bars and walls
- are within easy reach. Seated people use the walls of 36 in by
- 36 in (915 mm by 915 mm) showers for back support. Shower stalls
- that are 60 in (1525 mm) wide and have no curb may increase
- usability of a bathroom by wheelchair users because the shower
- area provides additional maneuvering space.
-
- A4.22 Toilet Rooms.
-
- A4.22.3 Clear Floor Space. In many small facilities, single- user
- restrooms may be the only facilities provided for all building
- users. In addition, the guidelines allow the use of "unisex" or
- "family" accessible toilet rooms in alterations when technical
- infeasibility can be demonstrated. Experience has shown that the
- provision of accessible "unisex" or single-user restrooms is a
- reasonable way to provide access for wheelchair users and any
- attendants, especially when attendants are of the opposite sex.
- Since these facilities have proven so useful, it is often
- considered advantageous to install a "unisex" toilet room in new
- facilities in addition to making the multi-stall restrooms
- accessible, especially in shopping malls, large auditoriums, and
- convention centers.
-
- Figure 28 (section 4.16) provides minimum clear floor space
- dimensions for toilets in accessible "unisex" toilet rooms. The
- dotted lines designate the minimum clear floor space, depending
- on the direction of approach, required for wheelchair users to
- transfer onto the water closet. The dimensions of 48 in (1220
- mm) and 60 in (1525 mm), respectively, correspond to the space
- required for the two common transfer approaches utilized by
- wheelchair users (see Fig. A6). It is important to keep in mind
- that the placement of the lavatory to the immediate side of the
- water closet will preclude the side approach transfer illustrated
- in Figure A6(b). To accommodate the side transfer, the space
- adjacent to the water closet must remain clear of obstruction for
- 42 in (1065 mm) from the centerline of the toilet (Figure 28) and
- the lavatory must not be located within this clear space. A
- turning circle or T-turn, the clear floor space at the lavatory,
- and maneuvering space at the door must be considered when
- determining the possible wall locations. A privacy latch or
- other accessible means of ensuring privacy during use should be
- provided at the door.
-
- RECOMMENDATIONS:
-
- 1. In new construction, accessible single-user restrooms may be
- desirable in some situations because they can accommodate a wide
- variety of building users. However, they cannot be used in lieu
- of making the multi-stall toilet rooms accessible as required.
-
- 2. Where strict compliance to the guidelines for accessible toilet
- facilities is technically infeasible in the alteration of
- existing facilities, accessible "unisex" toilets are a reasonable
- alternative.
-
- 3. In designing accessible single-user restrooms, the provisions
- of adequate space to allow a side transfer will provide
- accommodation to the largest number of wheelchair users.
-
- A4.23 Bathrooms, Bathing Facilities, and Shower Rooms.
-
- A4.23.3 Clear Floor Space. Figure A7 shows two possible
- configurations of a toilet room with a roll-in shower. The
- specific shower shown is designed to fit exactly within the
- dimensions of a standard bathtub. Since the shower does not have
- a lip, the floor space can be used for required maneuvering
- space. This would permit a toilet room to be smaller than would
- be permitted with a bathtub and still provide enough floor space
- to be considered accessible. This design can provide
- accessibility in facilities where space is at a premium (i.e.,
- hotels and medical care facilities). The alternate roll-in
- shower (Fig. 57b) also provides sufficient room for the "T-turn"
- and does not require plumbing to be on more than one wall.
-
- A4.23.9 Medicine Cabinets. Other alternatives for storing
- medical and personal care items are very useful to disabled
- people. Shelves, drawers, and floor-mounted cabinets can be
- provided within the reach ranges of disabled people.
-
- A4.26 Handrails, Grab Bars, and Tub and Shower Seats.
-
- A4.26.1 General. Many disabled people rely heavily upon grab
- bars and handrails to maintain balance and prevent serious falls.
- Many people brace their forearms between supports and walls to
- give them more leverage and stability in maintaining balance or
- for lifting. The grab bar clearance of 1-1/2 in (38 mm) required
- in this guideline is a safety clearance to prevent injuries
- resulting from arms slipping through the openings. It also
- provides adequate gripping room.
-
- A4.26.2 Size and Spacing of Grab Bars and Handrails. This
- specification allows for alternate shapes of handrails as long as
- they allow an opposing grip similar to that provided by a
- circular section of 1-1/4 in to 1-1/2 in (32 mm to 38 mm).
-
- A4.27 Controls and Operating Mechanisms.
-
- A4.27.3 Height. Fig. A8 further illustrates mandatory and
- advisory control mounting height provisions for typical
- equipment.
-
- Electrical receptacles installed to serve individual appliances
- and not intended for regular or frequent use by building
- occupants are not required to be mounted within the specified
- reach ranges. Examples would be receptacles installed
- specifically for wall-mounted clocks, refrigerators, and
- microwave ovens.
-
- A4.28 Alarms.
-
- A4.28.2 Audible Alarms. Audible emergency signals must have an
- intensity and frequency that can attract the attention of
- individuals who have partial hearing loss. People over 60 years
- of age generally have difficulty perceiving frequencies higher
- than 10,000 Hz. An alarm signal which has a periodic element to
- its signal, such as single stroke bells (clang-pause-clang-
- pause), hi-low (up-down-up-down) and fast whoop (on-off-on-off)
- are best. Avoid continuous or reverberating tones. Select a
- signal which has a sound characterized by three or four clear
- tones without a great deal of "noise" in between.
-
- A4.28.3 Visual Alarms. The specifications in this section do not
- preclude the use of zoned or coded alarm systems.
-
- A4.28.4 Auxiliary Alarms. Locating visual emergency alarms in
- rooms where persons who are deaf may work or reside alone can
- ensure that they will always be warned when an emergency alarm is
- activated. To be effective, such devices must be located and
- oriented so that they will spread signals and reflections
- throughout a space or raise the overall light level sharply.
- However, visual alarms alone are not necessarily the best means
- to alert sleepers. A study conducted by Underwriters Laboratory
- (UL) concluded that a flashing light more than seven times
- brighter was required (110 candela v. 15 candela, at the same
- distance) to awaken sleepers as was needed to alert awake
- subjects in a normal daytime illuminated room.
-
- For hotel and other rooms where people are likely to be asleep, a
- signal-activated vibrator placed between mattress and box spring
- or under a pillow was found by UL to be much more effective in
- alerting sleepers. Many readily available devices are sound-
- activated so that they could respond to an alarm clock, clock
- radio, wake-up telephone call or room smoke detector. Activation
- by a building alarm system can either be accomplished by a
- separate circuit activating an auditory alarm which would, in
- turn, trigger the vibrator or by a signal transmitted through the
- ordinary 110-volt outlet. Transmission of signals through the
- power line is relatively simple and is the basis of common,
- inexpensive remote light control systems sold in many department
- and electronic stores for home use. So-called "wireless"
- intercoms operate on the same principal.
-
- A4.29 Detectable Warnings.
-
- A4.29.2 Detectable Warnings on Walking Surfaces. The material
- used to provide contrast should contrast by at least 70%.
- Contrast in percent is determined by:
-
- Contrast = [(B1 - B2)/B1] x 100
-
- where B1 = light reflectance value (LRV) of the lighter area and
- B2 = light reflectance value (LRV) of the darker area.
-
- Note that in any application both white and black are never
- absolute; thus, B1 never equals 100 and B2 is always greater than
- 0.
-
- A4.30 Signage.
-
- A4.30.1 General. In building complexes where finding locations
- independently on a routine basis may be a necessity (for example,
- college campuses), tactile maps or prerecorded instructions can
- be very helpful to visually impaired people. Several maps and
- auditory instructions have been developed and tested for specific
- applications. The type of map or instructions used must be based
- on the information to be communicated, which depends highly on
- the type of buildings or users.
-
- Landmarks that can easily be distinguished by visually impaired
- individuals are useful as orientation cues. Such cues include
- changes in illumination level, bright colors, unique patterns,
- wall murals, location of special equipment or other architectural
- features.
-
- Many people with disabilities have limitations in movement of
- their heads and reduced peripheral vision. Thus, signage
- positioned perpendicular to the path of travel is easiest for
- them to notice. People can generally distinguish signage within
- an angle of 30 degrees to either side of the centerlines of their
- faces without moving their heads.
-
- A4.30.2 Character Proportion. The legibility of printed
- characters is a function of the viewing distance, character
- height, the ratio of the stroke width to the height of the
- character, the contrast of color between character and
- background, and print font. The size of characters must be based
- upon the intended viewing distance. A severely nearsighted
- person may have to be much closer to recognize a character of a
- given size than a person with normal visual acuity.
-
- A4.30.4 Raised and Brailled Characters and Pictorial Symbol Signs
- (Pictograms). The standard dimensions for literary Braille are
- as follows:
-
- Dot diameter .059 in.
-
- Inter-dot spacing .090 in.
-
- Horizontal separation between cells .241 in.
-
- Vertical separation between cells .395 in.
-
- Raised borders around signs containing raised characters may make
- them confusing to read unless the border is set far away from the
- characters. Accessible signage with descriptive materials about
- public buildings, monuments, and objects of cultural interest may
- not provide sufficiently detailed and meaningful information.
- Interpretive guides, audio tape devices, or other methods may be
- more effective in presenting such information.
-
- A4.30.5 Finish and Contrast. An eggshell finish (11 to 19 degree
- gloss on 60 degree glossimeter) is recommended. Research
- indicates that signs are more legible for persons with low vision
- when characters contrast with their background by at least 70
- percent. Contrast in percent shall be determined by:
-
- Contrast = [(B1 - B2)/B1] x 100
-
- where B1 = light reflectance value (LRV) of the lighter area and
- B2 = light reflectance value (LRV) of the darker area.
-
- Note that in any application both white and black are never
- absolute; thus, B1 never equals 100 and B2 is always greater than
- 0.
-
- The greatest readability is usually achieved through the use of
- light-colored characters or symbols on a dark background.
-
- A4.30.7 Symbols of Accessibility for Different Types of Listening
- Systems. Paragraph 4 of this section requires signage indicating
- the availability of an assistive listening system. An
- appropriate message should be displayed with the international
- symbol of access for hearing loss since this symbol conveys
- general accessibility for people with hearing loss. Some
- suggestions are:
-
- INFRARED
- ASSISTIVE LISTENING SYSTEM
- AVAILABLE
- ----PLEASE ASK----
-
- AUDIO LOOP IN USE
- TURN T-SWITCH FOR
- BETTER HEARING
- ----OR ASK FOR HELP----
-
- FM
- ASSISTIVE LISTENING
- SYSTEM AVAILABLE
- ----PLEASE ASK----
-
- The symbol may be used to notify persons of the availability of
- other auxiliary aids and services such as: real time captioning,
- captioned note taking, sign language interpreters, and oral
- interpreters.
-
- A4.30.8 Illumination Levels. Illumination levels on the sign
- surface shall be in the 100 to 300 lux range (10 to 30
- footcandles) and shall be uniform over the sign surface. Signs
- shall be located such that the illumination level on the surface
- of the sign is not significantly exceeded by the ambient light or
- visible bright lighting source behind or in front of the sign.
-
- A4.31 Telephones.
-
- A4.31.3 Mounting Height. In localities where the dial-tone first
- system is in operation, calls can be placed at a coin telephone
- through the operator without inserting coins. The operator
- button is located at a height of 46 in (1170 mm) if the coin slot
- of the telephone is at 54 in (1370 mm). A generally available
- public telephone with a coin slot mounted lower on the equipment
- would allow universal installation of telephones at a height of
- 48 in (1220 mm) or less to all operable parts.
-
- A4.31.9 Text Telephones. A public text telephone may be an
- integrated text telephone pay phone unit or a conventional
- portable text telephone that is permanently affixed within, or
- adjacent to, the telephone enclosure. In order to be usable with
- a pay phone, a text telephone which is not a single integrated
- text telephone pay phone unit will require a shelf large enough
- (10 in (255mm) wide by 10 in (255 mm) deep with a 6 in (150 mm)
- vertical clearance minimum) to accommodate the device, an
- electrical outlet, and a power cord. Movable or portable text
- telephones may be used to provide equivalent facilitation. A
- text telephone should be readily available so that a person using
- it may access the text telephone easily and conveniently. As
- currently designed pocket- type text telephones for personal use
- do not accommodate a wide range of users. Such devices would not
- be considered substantially equivalent to conventional text
- telephones. However, in the future as technology develops this
- could change.
-
- A4.32 Fixed or Built-in Seating and Tables.
-
- A4.32.4 Height of Tables or Counters. Different types of work
- require different table or counter heights for comfort and
- optimal performance. Light detailed work such as writing
- requires a table or counter close to elbow height for a standing
- person. Heavy manual work such as rolling dough requires a
- counter or table height about 10 in (255 mm) below elbow height
- for a standing person. This principle of high/low table or
- counter heights also applies for seated persons; however, the
- limiting condition for seated manual work is clearance under the
- table or counter.
-
- Table A1 shows convenient counter heights for seated persons.
- The great variety of heights for comfort and optimal performance
- indicates a need for alternatives or a compromise in height if
- people who stand and people who sit will be using the same
- counter area.
-
- TABLE A1
- CONVENIENT HEIGHTS OF TABLES AND COUNTERS FOR SEATED PEOPLE1
- SHORT WOMEN
- TALL MEN
- CONDITIONS OF USE
- in
- mm
- in
- mm
- Seated in a wheelchair:
- Manual work:
- Desk or removable
- armrests
- 26
- 660
- 30
- 760
- Fixed, full-size
- armrests2
- 323
- 815
- 323
- 815
- Light, detailed work:
- Desk or removable
- armrests
- 29
- 735
- 34
- 865
- Fixed, full-size
- armrests2
- 323
- 815
- 34
- 865
- Seated in a 16 in (405
- mm) high chair:
- Manual work
- 26
- 660
- 27
- 685
- Light, detailed work
- 28
- 710
- 31
- 7851All dimensions are based on a work-surface thickness of 1 1/2
- in (38 mm) and a clearance of 1 1/2 in (38 mm) between legs and
- the underside of a work surface.
-
- 2This type of wheelchair arm does not interfere with the
- positioning of a wheelchair under a work surface.
-
- 3This dimension is limited by the height of the armrests: a
- lower height would be preferable. Some people in this group
- prefer lower work surfaces, which require positioning the
- wheelchair back from the edge of the counter.
-
- A4.33 Assembly Areas.
-
- A4.33.2 Size of Wheelchair Locations. Spaces large enough for
- two wheelchairs allow people who are coming to a performance
- together to sit together.
-
- A4.33.3 Placement of Wheelchair Locations. The location of
- wheelchair areas can be planned so that a variety of positions
- within the seating area are provided. This will allow choice in
- viewing and price categories.
-
- Building/life safety codes set minimum distances between rows of
- fixed seats with consideration of the number of seats in a row,
- the exit aisle width and arrangement, and the location of exit
- doors. "Continental" seating, with a greater number of seats per
- row and a commensurate increase in row spacing and exit doors,
- facilitates emergency egress for all people and increases ease of
- access to mid-row seats especially for people who walk with
- difficulty. Consideration of this positive attribute of
- "continental" seating should be included along with all other
- factors in the design of fixed seating areas.
-
- A4.33.6 Placement of Listening Systems. A distance of 50 ft (15
- m) allows a person to distinguish performers' facial expressions.
-
- A4.33.7 Types of Listening Systems. An assistive listening
- system appropriate for an assembly area for a group of persons or
- where the specific individuals are not known in advance, such as
- a playhouse, lecture hall or movie theater, may be different from
- the system appropriate for a particular individual provided as an
- auxiliary aid or as part of a reasonable accommodation. The
- appropriate device for an individual is the type that individual
- can use, whereas the appropriate system for an assembly area will
- necessarily be geared toward the "average" or aggregate needs of
- various individuals. A listening system that can be used from
- any seat in a seating area is the most flexible way to meet this
- specification. Earphone jacks with variable volume controls can
- benefit only people who have slight hearing loss and do not help
- people who use hearing aids. At the present time, magnetic
- induction loops are the most feasible type of listening system
- for people who use hearing aids equipped with "T-coils," but
- people without hearing aids or those with hearing aids not
- equipped with inductive pick-ups cannot use them without special
- receivers. Radio frequency systems can be extremely effective
- and inexpensive. People without hearing aids can use them, but
- people with hearing aids need a special receiver to use them as
- they are presently designed. If hearing aids had a jack to allow
- a by-pass of microphones, then radio frequency systems would be
- suitable for people with and without hearing aids. Some
- listening systems may be subject to interference from other
- equipment and feedback from hearing aids of people who are using
- the systems. Such interference can be controlled by careful
- engineering design that anticipates feedback sources in the
- surrounding area.
-
- Table A2, reprinted from a National Institute of Disability and
- Rehabilitation Research "Rehab Brief," shows some of the
- advantages and disadvantages of different types of assistive
- listening systems. In addition, the Architectural and
- Transportation Barriers Compliance Board (Access Board) has
- published a pamphlet on Assistive Listening Systems which lists
- demonstration centers across the country where technical
- assistance can be obtained in selecting and installing
- appropriate systems. The state of New York has also adopted a
- detailed technical specification which may be useful.
-
- Table A2. Summary of Assistive Listening Devices
-
- System
- Advantages
- Disadvantages
- Typical
- Applications
- Induction Loop
- Transmitter:
- Transducer
- wired to
- induction
- loop around
- listening
- area.
- Receiver:
- Self-
- contained
- induction
- receiver or
- personal
- hearing aid
- with
- telecoil.
- Cost-Effective
- Low
- Maintenance
- Easy to use
- Unobtrusive
- May be
- possible to
- integrate
- into
- existing
- public
- address
- system.
- Some hearing
- aids can
- function as
- receivers.
- Signal spills
- over to
- adjacent
- rooms.
- Susceptible to
- electrical
- interference.
- Limited
- portability
- Inconsistent signal
- strength
- Head position affects
- signal
- strength.
- Lack of
- standards
- for
- induction
- coil
- performance.
- Meeting areas
- Theaters
- Churches and
- Temples
- Conference
- rooms
- Classrooms
- TV viewing
- FM
- Transmitter:
- Flashlight-
- sized worn
- by speaker.
- Receiver:
- With
- personal
- hearing aid
- via DAI or
- induction
- neck-loop
- and
- telecoil; or
- self-
- contained
- with
- earphone(s).
- Highly
- portable
- Different
- channels
- allow use by
- different
- groups
- within the
- same room.
- High user
- mobility
- Variable for
- large range
- of hearing
- losses.
- High cost of
- receivers
- Equipment
- fragile
- Equipment
- obtrusive
- High
- maintenance
- Expensive to
- maintain
- Custom fitting to
- individual user may be required.
- Classrooms
- Tour groups
- Meeting areas
- Outdoor
- events
- One-on-one
- Infrared
- Transmitter:
- Emitter in
- line-of-
- sight with
- receiver.
- Receiver:
- Self-
- contained.
- Or with
- personal
- hearing aid
- via DAI or
- induction
- neckloop and
- telecoil.
- Easy to use
- Insures
- privacy or
- confidential
- ity
- Moderate cost
- Can often be
- integrated
- into
- existing
- public
- address
- system.
- Line-of-sight
- required
- between
- emitter and
- receiver.
- Ineffective
- outdoors
- Limited
- portability
- Requires
- installation
- Theaters
- Churches and
- Temples
- Auditoriums
- Meetings requiring confidential ity
- TV viewing
- Source: Rehab Brief, National Institute on Disability and
- Rehabilitation Research, Washington, DC, Vol. XII, No. 10,
- (1990).
-
- A5.0 Restaurants and Cafeterias.
-
- A5.1 General. Dining counters (where there is no service) are
- typically found in small carry-out restaurants, bakeries, or
- coffee shops and may only be a narrow eating surface attached to
- a wall. This section requires that where such a dining counter
- is provided, a portion of the counter shall be at the required
- accessible height.
-
- A7.0 Business and Mercantile.
-
- A7.2(3) Assistive Listening Devices. At all sales and service
- counters, teller windows, box offices, and information kiosks
- where a physical barrier separates service personnel and
- customers, it is recommended that at least one permanently
- installed assistive listening device complying with 4.33 be
- provided at each location or series. Where assistive listening
- devices are installed, signage should be provided identifying
- those stations which are so equipped.
-
- A7.3 Check-out Aisles. Section 7.2 refers to counters without
- aisles; section 7.3 concerns check-out aisles. A counter without
- an aisle (7.2) can be approached from more than one direction
- such as in a convenience store. In order to use a check-out
- aisle (7.3), customers must enter a defined area (an aisle) at a
- particular point, pay for goods, and exit at a particular point.
-